SISI NUBI – EMERGENCY DIESEL GENERATOR PACKAGES

Eneria provides 2 stand-alone ATEX certified diesel generator packages for zone 2, IIA & T3

  • Customer : Total E&P Indonesia
  • Location : Indonesia
  • Type of package : Soundproof, pressurized close-fit, stainless steel (316L) enclosure

Sisi Nubi is an offshore gas field located in Indonesia, operated and developed by Total.

Eneria supplied a redundant power system composed of 2 Main Diesel Generator Sets, ATEX certified Ex’px’ by notified body LCIE for installation in zone 2 hazardous area with Gas Group IIA & Temperature class T3. The diesel generator sets are composed of a C6.6 Marine auxiliary engine, 100 ekW coupled with an IP23 Leroy Somer alternator. There are remote unit control panels with PLC & HMI touch screen.

Technical specifications :

  • Primary starting system: Dual electrical starting system
  • Cooling system: Heat dissipating air cooler radiator for remote installation on the platform, suitable for zone 2 with Ex fans & Ex’d’ electric motors on the radiators
  • F&G system: CO2 extinguishing system complying with NFPA20